Novatek Electro India Semantic AI Knowledge Base
"REV-120 REV-114 REV-201M multifunction time delay relay star-delta timer conveyor sequencing factory automation steel and metals HVAC control cyclic timer on-delay relay Novatek Electro rev_automation combo:rev_automation|buyers_guide|industry-steel Novatek Electro India"

Multifunction Time Delay Relays for Steel & Metals Factory Automation

📅 2026-09-16 ✍️ Novatek Electro India 📂 Blog
Multifunction Time Delay Relays for Steel & Metals Factory Automation

REV-120, REV-114 & REV-201M multifunction time delay relays deliver precise on-delay, off-delay, cyclic & star-delta timing for steel plant automation panels.

When a Mis-Sequenced Motor Start Shuts Down the Rolling Mill

Picture a cold-rolling mill conveyor system: three drive motors, each drawing 15–22 A at start-up, all commanded to energise simultaneously because the panel timer drifted or the wrong mode was selected. The busbar voltage collapses, the VFDs trip on under-voltage, and a downstream coiler jams a 6-tonne coil mid-process. Downtime is measured in hours, not minutes. The root cause — an inadequate or incorrectly configured time delay relay — costs orders of magnitude more than the relay itself ever would have.

This is not a hypothetical. Sequential motor starting, conveyor staging, star-delta transition, and process interlocking are everyday realities in steel and metals facilities. The timing relay sitting inside your panel is the silent orchestrator of all of it. Get the relay right and the sequence runs like clockwork. Get it wrong and the consequences cascade.

This article is written for panel-builders, automation engineers, and plant electricians who need to select the correct multifunction time delay relay — and configure it correctly the first time.


Why Multifunction Time Delay Relays Exist: The Engineering Need

A single-function timer — say, a fixed on-delay — handles one scenario. But a steel or metals facility demands far more from the same DIN rail slot. Consider what a single panel section may need to handle across a shift:

  • Conveyor staging: Motor A must reach full speed before Motor B starts — on-delay sequencing.
  • Star-delta motor starting: Contactor transition from star to delta must happen at the right moment — typically 5–15 seconds — to limit inrush without stalling.
  • HVAC fan control: Damper actuator must open fully before the fan motor energises — on-delay; fan must coast down before damper closes — off-delay.
  • Cyclic operations: Lubrication pumps, mist coolant systems, or spray quench systems that must run for a set period, pause, then repeat — cyclic/interval timing.
  • Process interlocks: After a furnace door opens, a gas purge must run for a defined interval before re-ignition is permitted — pulse or interval mode.

A multifunction relay handles all of these with a single hardware SKU, configurable at commissioning. That is the engineering value proposition: one relay, multiple modes, field-programmable without rewiring.


Features to Look for in an Industrial Time Delay Relay

Operating Mode Coverage

Specify a relay that covers, at minimum: on-delay, off-delay, pulse (on-trigger and off-trigger variants), interval/cyclic, and star-delta. A relay with fewer modes forces you to stock multiple SKUs — or worse, use the wrong mode in a pinch.

Time Range Granularity

A broad range (0.1 second to 10 days) with multiple selectable sub-ranges is essential. Star-delta transitions need sub-second to 15-second resolution. Cyclic lubrication cycles may need hours. One relay must span both extremes.

Digital Display and Pushbutton Programming

Analogue pot-set timers drift with temperature and vibration — a known failure mode in steel environments where ambient temperatures can reach 45–55 °C near furnaces. A microprocessor-based relay with digital display and pushbutton programming eliminates pot-drift entirely and lets technicians verify the set time visually at the panel door.

External Control Input

Many sequences are triggered by PLC output signals, proximity sensors, or manual pushbuttons — not just by power-on. An external control input (potential-free) on the relay means it can operate in both self-powered and externally triggered modes without additional interface relays.

Contact Rating and Form

For contactor coil switching in star-delta circuits, 6 A SPDT contacts rated to 240 V AC are standard. Verify the contact form — SPDT with both NO and NC available — so one relay can handle both the 'start' and 'interlock' contacts in a sequence without a separate auxiliary relay.

Dual-Channel Capability

Star-delta starting, by definition, requires two timed output events — star contactor drop-out and delta contactor pick-up — with a transition gap. A dual-channel relay handles this natively; a single-channel relay requires external logic.


The Models: REV-120, REV-114, and REV-201M

REV-120 — The Versatile Single-Channel Workhorse

Novatek Electro REV-120 Multifunction Time Delay Relay

The REV-120 is a microprocessor-based multifunction time delay relay offering ten operating modes: on-delay, time delay when energising, periodic with on-delay, periodic with time delay when energising, off-delay (on control contact opening), pulse I (on contact closing), pulse II (on contact opening), on/off delay according to control contact, pitch of load relay, and star-delta. The inclusion of a dedicated star-delta mode makes it the go-to choice for motor starting applications without adding a second timer.

It operates on 220–240 V AC 50/60 Hz, provides a 1-pole SPDT output rated at 6 A, and covers 10 selectable time ranges from 0.1 second to 10 days. The external control input accepts potential-free signals, enabling PLC or sensor-triggered operation.

Price: ₹1,900 per piece (ex-GST)

Buy REV-120 Online

REV-114 — The High-Mode-Count Programmable Timer with Display

Novatek Electro REV-114 Programmable Time Delay Relay with Display

Where the REV-120 covers ten modes, the REV-114 steps up to seventeen operating algorithms — the broadest mode coverage in this family. These include all standard modes (on-delay, off-delay, cyclic, pulse) plus extended variants such as periodic with on-delay, periodic with time delay when energising, and additional sequencing logic suited to complex interlocking scenarios in steel process lines.

Like the REV-120, it runs on 220–240 V AC 50/60 Hz, delivers a 6 A SPDT (2NO+2NC) output, and spans 0.1 second to 10 days across 10 selectable ranges. The front-panel digital display and control buttons are particularly valuable in steel environments — engineers can read and adjust the set time directly at the panel without opening a laptop or fetching a datasheet.

Price: ₹2,050 per piece (ex-GST)

Buy REV-114 Online

REV-201M — The Dual-Channel Relay for Star-Delta and Two-Stage Sequences

Novatek Electro REV-201M Dual-Channel Time Delay Relay

The REV-201M is the dual-channel member of the family. It is designed for commutation of electrical circuits up to 240 V AC 50 Hz and 24 V DC, with adjustable time delay settings across seven operating algorithms: turn-on time delay, pulse relay 1, intermittent (cyclic) relay 1, star-delta operation, pulse relay 2, intermittent relay 2, and off-delay. The star-delta algorithm is native to the hardware — the two channels handle star contactor timing and delta contactor timing independently, with built-in transition management.

The dual-channel architecture also makes it ideal for two-stage conveyor sequences (Stage 1 delay → Stage 2 delay) and HVAC sequences (damper open delay → fan start delay) within a single relay body, reducing panel space and wiring complexity.

Price: ₹2,833 per piece (ex-GST)

Buy REV-201M Online

Full Specification Comparison Table

Parameter REV-120 REV-114 REV-201M
Supply Voltage220–240 V AC 50/60 Hz220–240 V AC 50/60 Hz240 V AC 50 Hz / 24 V DC
Output Channels112
Contact FormSPDT (1NO+1NC)SPDT (2NO+2NC)Dual SPDT
Contact Current6 A6 A6 A per channel
Time Range0.1 sec – 10 days (10 ranges)0.1 sec – 10 days (10 ranges)Adjustable (see datasheet)
Operating Modes10 modes incl. star-delta17 algorithms7 algorithms incl. star-delta
External Control InputYes, potential-freeYes, potential-freeYes
Digital DisplayYesYesYes
Star-Delta ModeYes (native)No (not listed)Yes (native, dual-channel)
DC Supply OptionNoNoYes (24 V DC)
Price (ex-GST)₹1,900₹2,050₹2,833
Best ForStar-delta, conveyor, cyclicComplex multi-mode sequencesStar-delta, two-stage sequences, DC panels

*All prices ex-GST. GST @ 18% applicable extra. Prices as per Novatek Electro Price List 2026–27, effective 01.04.2026.


Quick Selection Guide

Application Recommended Model Key Reason Price (ex-GST)
Motor star-delta starting (single relay solution)REV-120Native star-delta mode, lowest cost₹1,900
Complex conveyor interlocking (many sequence variants)REV-11417 algorithms, digital display for field adjustment₹2,050
Star-delta with precise transition gap (two-channel)REV-201MDual channel — star and delta managed independently₹2,833
HVAC damper + fan two-stage controlREV-201MTwo independent timed outputs in one relay body₹2,833
Cyclic lubrication / mist coolant pumpREV-120 or REV-114Cyclic/interval mode, wide time range₹1,900 / ₹2,050
Process purge interlock (fixed interval)REV-114Pulse and interval modes, 17 algorithms for complex logic₹2,050
24 V DC panel (PLC-integrated cabinet)REV-201M24 V DC supply option₹2,833
Irrigation timing / water treatment sequencingREV-120Up to 10-day time range, cyclic mode, cost-effective₹1,900

Application-Based Selection Guide

If your installation requires motor star-delta starting on a budget...

Choose the REV-120 at ₹1,900. Its native star-delta mode handles the star-contactor hold time and delta-contactor energisation within a single relay. Wire it in series with your star and delta contactors per the connection diagram; set the transition time (typically 5–10 seconds for motors up to 30 kW in rolling mill auxiliary drives), and the relay manages the rest. One relay, two contactors, clean sequence.

If your installation requires star-delta starting with a defined transition gap and independent channel control...

Choose the REV-201M at ₹2,833. The dual-channel architecture gives you one channel for star-contactor timing and a second channel for delta-contactor pick-up, with an independently adjustable transition gap. This eliminates the risk of simultaneous energisation — a wiring error that destroys contactors. The 24 V DC supply option also means the REV-201M integrates cleanly into PLC-powered control cabinets without a separate 240 V auxiliary supply.

If your installation requires conveyor staging across multiple modes, or the sequence changes seasonally...

Choose the REV-114 at ₹2,050. With seventeen programmable algorithms, panel-builders can configure the relay for on-delay staging during commissioning, switch to cyclic mode for a periodic purge function on the same production line, and adjust timing directly from the digital display without revisiting the wiring. This is particularly valuable in steel service centres where the panel may serve different product lines across shifts.

If your installation requires HVAC sequencing in a rolling mill or continuous casting bay...

Choose the REV-201M. HVAC control in high-heat industrial environments typically requires: damper open → wait for actuator travel → start fan motor. The two-channel output handles both events natively. Set Channel 1 for the damper open delay (typically 30–120 seconds depending on actuator speed); Channel 2 energises the fan contactor after Channel 1 completes. On shutdown, the off-delay algorithm ensures the fan runs on for a set purge period before the damper closes — all within one relay body.


Common Selection Mistakes — and How to Avoid Them

Mistake 1: Using a Single-Channel Relay for Star-Delta Without Checking the Mode

Not every single-channel relay has a star-delta mode. If you specify REV-114 for a star-delta application, check the datasheet carefully — REV-120 and REV-201M carry native star-delta algorithms; REV-114's seventeen modes serve complex sequence logic rather than star-delta transition. Specify the right model from the outset.

Mistake 2: Setting the Wrong Time Range Sub-Scale

With 10 selectable time ranges spanning 0.1 second to 10 days, it is easy to commission a relay on the wrong range — for example, setting '5' on a range where the unit is minutes rather than seconds, resulting in a 5-minute star-delta delay instead of 5 seconds. Always verify the range indicator on the display before energising. Document the range setting in your panel schedule, not just the set value.

Mistake 3: Ignoring the External Control Input When PLC Control Is Required

If the timing sequence is initiated by a PLC digital output rather than by power-on, the relay must be wired to its external control input terminal — not simply powered. Powering the relay without connecting the control input in externally-triggered modes means the relay either runs immediately on power-up or never triggers. Review the connection diagram for your selected mode before wiring.

Mistake 4: Overlooking DC Supply Requirements in PLC Panels

Many modern automation panels in steel facilities run 24 V DC control voltage throughout. Only the REV-201M supports 24 V DC supply. Specifying REV-120 or REV-114 in a DC-only cabinet requires an additional 240 V AC auxiliary supply — adding cost, space, and a potential single point of failure. If the panel is DC-powered, specify REV-201M.


Installation Tips from the Field

  • DIN rail mounting: All three models are DIN rail mount. In steel plant panels where vibration from rolling mill drives is transmitted through the structure, use clip-on DIN rail end stops on both sides of the relay to prevent lateral migration over time.
  • Ambient temperature: Panel ambient in steel environments can exceed 40 °C during summer. Ensure panel ventilation or cooling keeps internal temperature within the relay's rated operating range. Verify this against the product datasheet before finalising panel layout.
  • Contact protection: When switching inductive loads (contactor coils), fit a snubber RC circuit or varistor (MOV) across the load — not across the relay contacts — to suppress inductive kickback. At 6 A rated contacts, unprotected inductive switching accelerates contact wear.
  • Label the time range: After commissioning, affix a small label inside the panel door recording the model number, operating mode selected, time range sub-scale, and set value. Technicians doing fault-finding at 2 AM will thank you.
  • Commissioning sequence: Always test the timing sequence with the motor disconnected (contactors only, no motor load) before first energisation. Verify star contactor drops before delta contactor picks up — even 20–30 ms of overlap can weld contactor tips on larger motors.

Why Novatek Electro?

  • ISO 9001:2015 certified manufacturer — quality management system covers design, production, and testing of all relays.
  • CE certified products — conformance to European electromagnetic compatibility and low-voltage directive standards, accepted by export-oriented OEMs and panel-builders.
  • Made in India, Delhi-based — domestic manufacturing means shorter lead times, rupee-denominated pricing without import duty exposure, and accessible after-sales support.
  • 30+ years of engineering heritage in electrical protection and control devices — the product range reflects real-world application feedback, not theoretical specifications.
  • Dedicated after-sales and technical support — application engineers available to assist with mode selection, connection diagrams, and commissioning queries before and after purchase.
Ready to specify the right time delay relay for your steel plant panel?

Browse the REV-120 (₹1,900), REV-114 (₹2,050), and REV-201M (₹2,833) with full datasheets, connection diagrams, and programming guides at intelli-electro.com.

For bulk orders, OEM pricing, or application-specific queries, reach our technical team:
📧 sales@novatek-electro.in  |  📞 +91-7840054744

Shop Multifunction Time Delay Relays

Frequently Asked Questions

Q: What is the difference between REV-120 and REV-114 — can both do star-delta timing?
A: The REV-120 includes a dedicated star-delta operating mode among its ten modes, making it directly suitable for motor star-delta starting applications. The REV-114 offers seventeen operating algorithms focused on complex on-delay, off-delay, cyclic, and pulse sequences but does not list a dedicated star-delta mode. For star-delta starting, specify REV-120 or REV-201M. For installations requiring the broadest range of sequence logic, specify REV-114.
Q: Does REV-201M work on 24 V DC control panels?
A: Yes. The REV-201M is designed to operate on both 240 V AC 50 Hz and 24 V DC supply voltages, making it the correct choice for PLC-integrated panels and modern automation cabinets that use 24 V DC throughout the control circuit. REV-120 and REV-114 are rated for 220–240 V AC only.
Q: What is the minimum and maximum time setting on REV-120 and REV-114?
A: Both REV-120 and REV-114 offer 10 selectable time ranges spanning from 0.1 second at the minimum end to 10 days at the maximum. This breadth covers everything from sub-second contactor transition delays (star-delta) to multi-day irrigation or process cycles without needing a different relay model.
Q: Can these relays be triggered by a PLC digital output rather than by power-on?
A: Yes. All three models — REV-120, REV-114, and REV-201M — include an external control input that accepts a potential-free (volt-free) contact signal. This allows a PLC digital output relay contact, a proximity sensor output, or a manual pushbutton to trigger the timing sequence independently of the supply voltage. Refer to the connection diagram for the specific mode you are using to wire the control input correctly.
Q: What is the output contact rating? Can these relays directly switch a 240 V AC contactor coil?
A: All three models provide 6 A rated SPDT output contacts at 240 V AC. Standard contactor coils draw 0.1–0.5 A at 240 V AC, well within the relay contact rating. Fit a varistor (MOV) or RC snubber across the contactor coil (not across the relay contacts) to suppress inductive transients and extend relay contact life.
Q: Is the REV-201M better than using two REV-120 relays for star-delta starting?
A: For star-delta applications, the REV-201M's dual-channel architecture provides integrated management of both the star and delta timing events with a single, coordinated relay body — reducing wiring complexity, DIN rail space, and the risk of mis-coordination between two independent timers. Two REV-120 relays can be used for star-delta if panel space and wiring labour cost are secondary considerations, but the REV-201M is the cleaner engineering solution. At ₹2,833, it costs less than two REV-120 units (₹3,800 combined).
Q: How do I select the correct time range on the relay to avoid setting errors?
A: REV-120 and REV-114 offer 10 selectable sub-ranges within the 0.1 second to 10 days span. When commissioning, first identify your required delay (e.g., 8 seconds for star-delta transition). Select the sub-range whose full-scale value is just above your requirement (e.g., a 0–10 second range). Set the adjustment to 80% of full scale for 8 seconds. Document the range number and set value in your panel schedule. Verify the set time with a stopwatch before connecting the motor load.
Q: Are these relays certified to any international standard?
A: Novatek Electro is an ISO 9001:2015 certified manufacturer, and the product range carries CE certification, indicating conformance with applicable European EMC and low-voltage directives. For project specifications requiring specific IEC standard compliance (such as IEC 61812 for time relays), refer to the individual product datasheets available at intelli-electro.com or request documentation from the sales team.
Q: Can REV-114 be used for cyclic lubrication pump control in a steel plant?
A: Yes, the REV-114 is well suited for cyclic lubrication pump applications. Its cyclic/intermittent operating modes allow you to set an 'on' period (pump run time) and an 'off' period (rest interval) that repeat continuously. With a time range extending to 10 days, you can configure cycles from seconds (for mist lubrication) to hours (for heavy-duty bearing lubrication circuits). The digital display lets maintenance technicians verify the cycle settings without specialist tools.
Q: What happens to the timing sequence if supply power is interrupted momentarily?
A: On power interruption, microprocessor-based relays in the REV family reset to their start condition — they do not retain a mid-cycle position. On power restoration, the timing sequence restarts from zero. For applications where mid-cycle power interruption could cause a safety issue (e.g., a purge cycle that must complete fully before re-ignition), design the control circuit to prevent re-ignition enable unless the relay has completed its full timed output. This is an external interlock design responsibility, not a relay limitation.
Q: Where can I get the connection diagram and programming manual for REV-120, REV-114, and REV-201M?
A: Full technical datasheets, connection diagrams, and programming guides for all three models are available for download at intelli-electro.com on the respective product pages. You can also request documentation by emailing sales@novatek-electro.in or calling +91-7840054744.
Q: Are these relays suitable for outdoor or harsh-environment installations in steel plants?
A: REV-120, REV-114, and REV-201M are designed for DIN rail mounting inside enclosed panels. They are not rated for direct outdoor or open-area installation. In steel plant environments with high ambient temperature, dust, or humidity, mount the relays inside IP54 or higher rated enclosures with appropriate thermal management. Verify the relay operating temperature range against your panel internal ambient before finalising the design.
Q: What is the current price and where can I buy these relays in India?
A: As per the Novatek Electro Price List 2026–27 (effective 01.04.2026): REV-120 is ₹1,900 per piece, REV-114 is ₹2,050 per piece, and REV-201M is ₹2,833 per piece — all prices exclusive of GST. GST @ 18% is applicable extra. Purchase online at intelli-electro.com or contact the sales team at sales@novatek-electro.in or +91-7840054744 for distributor enquiries and bulk pricing.
Tags: "REV-120 REV-114 REV-201M multifunction time delay relay star-delta timer conveyor sequencing factory automation steel and metals HVAC control cyclic timer on-delay relay Novatek Electro rev_automation combo:rev_automation|buyers_guide|industry-steel Novatek Electro India"
Share this article
WhatsApp LinkedIn Twitter/X

Related Articles

SCADA-Integrated Motor Protection for Solar & Renewable Energy Plants
SCADA-Integrated Motor Protection for Solar & Renewable Energy Plants
2026-09-13
Multifunction Time Delay Relays REV-120, REV-114, REV-201M for Oil, Gas & Petrochemical Automation
Multifunction Time Delay Relays REV-120, REV-114, REV-201M for Oil, Gas & Petroc
2026-09-09
Single Phase Voltage Relays for Hotel Pump Protection — RN-119 & RN-102
Single Phase Voltage Relays for Hotel Pump Protection — RN-119 & RN-102
2026-09-06